{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What is the current measurement accuracy of the Micrologic 2.0A, 3.0A, 5.0A, and 6.0A trip units with ammeter?
Issue:
What is the current measurement accuracy of the Micrologic 2.0A, 3.0A, 5.0A, and 6.0A trip units with ammeter?

Product Line:
Powerpact P, R, Masterpact NW, NT

Resolution:
They provide continuous current measurements from 0.2 to 20x In and are accurate to within 1.5% (including the sensors).
Below 0.05x In, measurements are not significant. Between 0.05-0.2x In, accuracy is to within 0.5% In + 1.5% of the reading.

The optional external power supply makes it possible to display currents < 20% In.

A digital LCD screen continuously displays the most heavily loaded phase (Imax) or displays the I1, I2, I3, IN, Ig, IΔn, stored-current (maximeter) and setting values by successively pressing the navigation button.

Micrologic A control units measure the true RMS value of currents.

Schneider Electric USA

Attachment(s)
Micrologic Accuracy calculation.pdf [77.36 KB]
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.