Video: Installing HRK4060 Class R Fuse Kit on Heavy Duty Safety Switches
Issue:
How is a HRK4060 Class R Fuse Kit installed into the correct Heavy Duty Safety Switch fuse clips?
Product Line:
Heavy Duty Safety Switches
Environment:
Class R Fuse Rejection Kit
Resolution:
NOTE: The HRK4060 Class R fuse kits are design to be installed in the switches to REJECT all But Class R fuses. The Kit contains three rejection pins and collars, one per pole of a 3-pole switch.
The HRK4060 is designed ONLY for use with 400amp to 600amp, 240Vac and 600Vac Heavy Duty Safety Switches.
Also, follow ALL the steps in the instructions.(See below attached the kit instructions)
The equipment must be installed and serviced only by qualified electrical personnel.
Make sure to turn OFF ALL Power supplying the equipment and verify the power is OFF using a properly rated voltage sensing device, BEFORE working on or with electrical equipment.

CAUTION: TURN OFF AND DISCONNECT POWER AHEAD OF SWITCH BEFORE INSTALLING FUSE ADAPTERS.
DO NOT USE RENEWABLE LINK FUSES IN FUSED SWITCHES.
Once all Safety steps are followed, begin the kit installation by following the steps in the instructions.
1) Insert the long pin through the hole in the load side fuse clip, and then through the collar.
2) Push the collar FIRMLY onto the pin. A pair of pliers may be required to push the collar onto the rejection pin. The collar should not be removable once properly installed.
NOTE: BE CAREFUL NOT TO BREAK ADJACENT MOLDED INSULATORS WHEN INSTALLING ADAPTER KIT.
How is a HRK4060 Class R Fuse Kit installed into the correct Heavy Duty Safety Switch fuse clips?
Product Line:
Heavy Duty Safety Switches
Environment:
Class R Fuse Rejection Kit
Resolution:
NOTE: The HRK4060 Class R fuse kits are design to be installed in the switches to REJECT all But Class R fuses. The Kit contains three rejection pins and collars, one per pole of a 3-pole switch.
The HRK4060 is designed ONLY for use with 400amp to 600amp, 240Vac and 600Vac Heavy Duty Safety Switches.
Also, follow ALL the steps in the instructions.(See below attached the kit instructions)
The equipment must be installed and serviced only by qualified electrical personnel.
Make sure to turn OFF ALL Power supplying the equipment and verify the power is OFF using a properly rated voltage sensing device, BEFORE working on or with electrical equipment.
CAUTION: TURN OFF AND DISCONNECT POWER AHEAD OF SWITCH BEFORE INSTALLING FUSE ADAPTERS.
DO NOT USE RENEWABLE LINK FUSES IN FUSED SWITCHES.
Once all Safety steps are followed, begin the kit installation by following the steps in the instructions.
1) Insert the long pin through the hole in the load side fuse clip, and then through the collar.
2) Push the collar FIRMLY onto the pin. A pair of pliers may be required to push the collar onto the rejection pin. The collar should not be removable once properly installed.
NOTE: BE CAREFUL NOT TO BREAK ADJACENT MOLDED INSULATORS WHEN INSTALLING ADAPTER KIT.
Released for: Schneider Electric USA
Attachment(s)
Explore more
Product:
Explore more
Product:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.