Issue:
Panelboard lug temperature rating
Product Line:
Panelboard
Environment:
NQ Panelboards
Resolution:
The NQ 100 amp MAIN LUG panel is the only panelboard that allows the termination of conductors rated at 60 degree C, it has a dual listing (60/75 deg C).
ALL other panels have 75 deg C rated terminations and require 75 deg C conductors. Conductors with higher temperature ratings may be terminated on lower temperature rated terminations provided the ampacity of the conductor is based on the lower rating from table 310-16 in the NEC. For example, a 3/0 copper conductor with a 90 deg C temperature rating is rated at 225 amps, but you have to apply it at the 75 deg C rating from the table which is derated to 200 amps.
Panelboard lug temperature rating
Product Line:
Panelboard
Environment:
NQ Panelboards
Resolution:
The NQ 100 amp MAIN LUG panel is the only panelboard that allows the termination of conductors rated at 60 degree C, it has a dual listing (60/75 deg C).
ALL other panels have 75 deg C rated terminations and require 75 deg C conductors. Conductors with higher temperature ratings may be terminated on lower temperature rated terminations provided the ampacity of the conductor is based on the lower rating from table 310-16 in the NEC. For example, a 3/0 copper conductor with a 90 deg C temperature rating is rated at 225 amps, but you have to apply it at the 75 deg C rating from the table which is derated to 200 amps.
Released for: Schneider Electric USA






Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.