Multi-9 C60 Breakers: Values for watts loss and voltage drop per pole
Issue:
Power Loss
Product Line:
Circuit Breakers
Resolution:
The attached document gives the power loss (watts loss) and voltage drop per pole at rated current of the breaker (nominal current). For example, a 1 A breaker would be expected to have a watts loss per pole of 2.3 W at rated current of 1 A. This information can be used to calculate voltage drop when used at other than nominal current.
Power Loss
Product Line:
Circuit Breakers
Resolution:
The attached document gives the power loss (watts loss) and voltage drop per pole at rated current of the breaker (nominal current). For example, a 1 A breaker would be expected to have a watts loss per pole of 2.3 W at rated current of 1 A. This information can be used to calculate voltage drop when used at other than nominal current.