How can we help you today?

What are a ZB2BH6 and ZB2BH5?

Issue:
ZB2BH6 and ZB2BH5 Difference

Product Line:
Push Buttons and Operator Interface

Environment:
ZB2 Push Buttons

Resolution:
(Obsoleted) ZB2BH5 is a push on, push off yellow extended head non-illuminated pushbutton.
(Obsoleted) ZB2BH6 is a push on, push off blue extended head non-illuminated pushbutton.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings