How does a dry type transformer, 600V and below perform at a high altitude? Is there a derating factor that needs to be considered for high elevation environment?
Issue:
What derating factors need to be considered for High altitude installation of Low Voltage dry type transformers?
Product Line:
LV Dry Type Transformers
Environment:
Application
Cause:
Product features
Resolution:
The effectiveness of the ambient air to remove/carry away heat from a transformer is reduced at higher altitudes due to air`s lower density at those elevations.
The derating factor is 0.3% for every 330 FT over 3300 FT, or 0.3% for each 100 meters above 1000 meters.
For example, if a transformer is being used at 13,050FT, the deration factor is = ( 13,050 FT - 3300 Total derating factor) / 330 FT = 29.54 ... round up to 30... 30 X 0.3 = 9% derating, or 91% capacity available.
What derating factors need to be considered for High altitude installation of Low Voltage dry type transformers?
Product Line:
LV Dry Type Transformers
Environment:
Application
Cause:
Product features
Resolution:
The effectiveness of the ambient air to remove/carry away heat from a transformer is reduced at higher altitudes due to air`s lower density at those elevations.
The derating factor is 0.3% for every 330 FT over 3300 FT, or 0.3% for each 100 meters above 1000 meters.
For example, if a transformer is being used at 13,050FT, the deration factor is = ( 13,050 FT - 3300 Total derating factor) / 330 FT = 29.54 ... round up to 30... 30 X 0.3 = 9% derating, or 91% capacity available.
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.