Can a 2p, HOM-GFI breaker be used in the HOM24L70F, HOM24L70S, and HOM24L70RB load centers?

Issue:
What Homeline GFI breakers will work with the HOM24L70F, HOM24L70S, and HOM24L70RB load centers?

Product Line:
Homeline load centers

Resolution:
HOM215GFI, HOM220GFI and HOM230GFI breakers can be used in the HOM24L70F, S, or RB load centers due to adequate wire bending space for a maximum #10 AWG wire. This will restrict the HOM-GFI breaker to a maximum of 30 amperes.