Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
When an I-Line panel is being fed by dual power sources (Generator, UPS, etc.) and a main utility feed, can a mechanical interlock be used between these back-fed main breakers so only 1 breaker can be energized at a time?
Issue:
Can a Generator Interlock Kit be used on a ILine Panelboard?

Product Line:
Panelboard

Environment:
I-Line Power Distribution Panelboards

Resolution:
A mechanical interlock should never be used when a panel is being fed by 2 separate sources. Some kind of key locking device needs to be used. A key interlock needs to be used on both breakers.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings