How can we help you today?

What is the amount of current imbalance required to trip the feature unit 9065 solid state overload relay?

Issue:
When will a Solid State Overload trip when there is current Imbalance

Product Line:
NEMA and Definite Purpose Contactors and Starter

Environment:
9065 Solid State Overload Relay

Resolution:
The unit is guaranteed to trip within 3 seconds at 25% phase current imbalance. It will start tripping at +/- 17% imbalance.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.