Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do you replace a coil on an 8910DPA92 contactor?
Issue:
What are the instructions to remove the coil on a DPA9* Contactor?

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
Class 8910 Type DPA Contactors

Resolution:
Loosen and remove the four screws on the back of the contactor. Take the back off and set it aside. Remove the E-shaped magnet. Take the coil out and drop a new coil in its place. Reverse the above procedure.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings