What is the recommended hanger spacing for CP50410 style of busway?
Issue:
What is the hanger spacing to be used for CP50410?
Product Line:
Low Voltage and Medium Voltage Busway
Environment:
I-line Busway
Resolution:
The busway must be supported at least every 10 feet when mounted horizontally flatwise, at least every 5 feet when mounted edgewise horizontally, or at least every 16 feet when mounted vertically.
What is the hanger spacing to be used for CP50410?
Product Line:
Low Voltage and Medium Voltage Busway
Environment:
I-line Busway
Resolution:
The busway must be supported at least every 10 feet when mounted horizontally flatwise, at least every 5 feet when mounted edgewise horizontally, or at least every 16 feet when mounted vertically.
Released for: Schneider Electric USA