How to order phase loss protection in a 8502/8536/8538/8539 Contactor - Starter?

Issue:
How does one specify phase loss protection on a combination or non-combination NEMA starter?

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
Type S NEMA Contactors and Starters

Resolution:
Order class 8538/8539 or Class 8536/8502 with form R44. Specify voltage of motor and control devices. Provides phase failure phase reversal over and under voltage protection.