What is the rating of the number of switching operations of Square D, 200 A, general duty, F-series safety switches?

Product Line:
GD SS

Resolution:
For safety switches, the standard for design and testing of the number of switching operations is governed by UL98 and NEMA KS-1. There are two separate tests: (1) Endurance Test, and (2) Horsepower-overload test. The below table shows the minimum number of operations required (OFF to ON to OFF) by UL and NEMA. For the endurance test, however, Square D F series safety switches exceed the UL and NEMA requirements by up to 3 times the total (see below table):

NUMBER OF OPERATIONS
Square D Safety Switches (F series)
200 A, General Duty

Endurance Test Number of OpsHP Test Number of Ops
Test StandardAt Rated Load*No LoadTotal (L+NL)At Rated HP
UL60002000800010
NEMA 60002000800010
Square D6000180002400010

*Endurance test done at switch rated load current
**Horsepower test - make/break motor inrush/locked rotor current at rated HP

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings