What is the rating of the number of switching operations of Square D, 200 A, general duty, F-series safety switches?
Product Line:
GD SS
Resolution:
For safety switches, the standard for design and testing of the number of switching operations is governed by UL98 and NEMA KS-1. There are two separate tests: (1) Endurance Test, and (2) Horsepower-overload test. The below table shows the minimum number of operations required (OFF to ON to OFF) by UL and NEMA. For the endurance test, however, Square D F series safety switches exceed the UL and NEMA requirements by up to 3 times the total (see below table):
NUMBER OF OPERATIONS
Square D Safety Switches (F series)
200 A, General Duty
| Endurance Test Number of Ops | HP Test Number of Ops | |||
| Test Standard | At Rated Load* | No Load | Total (L+NL) | At Rated HP |
| UL | 6000 | 2000 | 8000 | 10 |
| NEMA | 6000 | 2000 | 8000 | 10 |
| Square D | 6000 | 18000 | 24000 | 10 |
*Endurance test done at switch rated load current
**Horsepower test - make/break motor inrush/locked rotor current at rated HP