What are the actual values of NEMA B600?
Issue:
NEMA B600 rating indicate?
Product Line:
NEMA and Definite Purpose Contactors and Starters
Environment:
NEMA Product Lines
Resolution:
Maximum continuous carry current of 5.00 amperes.
Maximum Current in amperes:
Volts Make Break
120 30.0 3.0
240 15.0 1.5
480 7.5 0.75
600 6.0 0.60
Maximum Volt-Amperes:
Make - 3600
Break - 360
NEMA B600 rating indicate?
Product Line:
NEMA and Definite Purpose Contactors and Starters
Environment:
NEMA Product Lines
Resolution:
Maximum continuous carry current of 5.00 amperes.
Maximum Current in amperes:
Volts Make Break
120 30.0 3.0
240 15.0 1.5
480 7.5 0.75
600 6.0 0.60
Maximum Volt-Amperes:
Make - 3600
Break - 360