Data Center Expert | Devices Stuck in Maintenance Mode After Upgrade to 7.8.1

Issue:
After upgrading to Data Center Expert version 7.8.1, devices are stuck in maintenance mode.

Product line:
StruxureWare Data Center Expert (DCE)
- Basic Appliance (AP9465)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
- Virtual Appliance (AP94VMACT)

Environment:
StruxureWare Data Center Expert (7.8.1)

Resolution:

In order to remove the device from maintenance mode, the device must first be entered into maintenance mode again.

1) Within the DCE Desktop Client, navigate to the Monitoring perspective:
ddce icons

2) Click on All Devices or the specific device group within the Device Groups pane that contains the device stuck in maintenance mode:
dce all devices

3) Within the Device View pane, right-click on the device stuck in maintenance mode and select Enter Maintenance Mode:
dce device view

4) Leave the default value of Now for Enter maintenance mode and Never for Exit maintenance mode and click OK:
dce main t mode

5) Right-click on the device stuck in maintenance mode and select Exit Maintenance Mode:
dce exit maint mode

6) Click OK to Exit Maintenance Mode for the device.
dce exit maint mode

The device should now have exited maintenance mode.  If it did not, please reach out to your local technical support for assistance.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.