How can we help you today?

What is the reset time for LRD thermal overload relay?

Unlike the LR9D solid state devices which have a specified automatic reset time, our LRD overloads are an electromechanical product and even when set on automatic reset we do not have reset time to provide.

The resetting time ( regardless of the specific product reference ) depends on :

- The kind of tripping ( IE: Thermal tripping, phase tripping, differential…. )

- The state of the overload ( IE: cold state, hot state )

- The ambient temperature

Combining all of these conditions leads to a variable time range before the reset can occur.

- The reset is allowed only when the internal bimetal sensors of the LRD** have come back to a position allowing reset.

- The bimetal sensor represents motor temperature and we need to cool down the motor prior to allowing a reset.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings