How can we help you today?

How many numbers of channels supported by BMENOR2200H in the IEC104 Server Configuration?

The BMENOR2200H supports a maximum of 4 channels when configured as IEC104 server configuration.

Note:
  • There is one main channel and the rest 3 of them are the virtual image of the main channel.
  • The events in all 4 channels are not synchronized among them. Duplicated across all 4 channels
  • To avoid the duplicated events the BMENOR2200H supports the IEC104 Server channel redundancy feature.