How can we help you today?
Why is the MOD_FLT of x80 DI/DO modules different between the local rack and the EIO rack?
In an M580 application, the device DDT associated with an X80 DI/DO module includes the MOD_FLT word.
For modules installed in an Ethernet RIO rack, background exchanges between the M580 CPU and the BMxCRA312x0 adapter update the device DDT.
The MOD_FLT information is not available for modules installed in the M580 local rack, including when using the READ_STS_MX EFB. This limitation is related to the M580 architecture.
To retrieve MOD_FLT for a module in an Ethernet RIO rack:
1- Enable Allow dynamic arrays (ANY_ARRAY_XXX) in EcoStruxure Control Expert:
- For M580 Safety: Tools > Project Settings > Scope: Process > Variables
- Standard M580: Tools > Project Settings > Variables
2- Create a section using the READ_STS_MX and ADDMX EFBs
3- Configure ADDMX with the IP address of the corresponding BMxCRA312x0 adapter
For more information, see page 306 of the "Modicon X80 Discrete Input/Output Modules User Manual".
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.