Altivar drive shows negative frequency but motor runs forward

Article available in these languages:

Issue:
How can you correct an issue where the motor runs forward but the display is showing negative frequency?

Resolution:

This typically indicates incorrect motor phase rotation. The drive must run in reverse, indicated by the negative frequency, for the motor to rotate in the intended direction.

To correct the motor rotation:

  1. Stop the drive and follow the appropriate electrical safety procedures.
  2. Swap any two motor leads.
  3. Restart the drive and issue a Forward Run command.
  4. Verify that the motor rotates in the correct direction and the displayed frequency is positive.

For systems with a bypass:
Verify the motor rotation in both drive and bypass modes.

  • Correct in bypass, incorrect in drive mode: Swap any two motor leads at the drive output (T terminals).
  • Correct in drive mode, incorrect in bypass: Swap two phases at the incoming power connection or at the input of the bypass contactor.
  • Incorrect in both drive and bypass modes: Swap any two phases at the motor connection.

Output Phase Rotation parameter:
Some Altivar drives allow the output phase rotation to be changed through a parameter. On ATV600, ATV900, and ATV340 drives, this is the PHR (Output Phase Rotation) parameter.

PHR can be useful for testing. However, physically correcting the wiring is recommended for a permanent solution because the parameter setting may be lost if the drive is reset to factory defaults.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.