NetBotz 4.x firmware: TLS auto-negotiates to the highest version
Issue:
TLS auto-negotiates to the highest version
Product Line:
NetBotz
Environment:
Botsware version 4.5.2 to 4.7
Cause:
TLS versions 1.0, 1.1, and 1.2 are available on a number of versions of NetBotz firmware. Version TLS 1.2 was added in version 4.5.2 and TLS 1.0 was removed in version 4.6.4
Resolution:
Although version 1.1 is still available, whatever system connects to the NetBotz appliance should auto-negotiate to the highest version of TLS available on both systems. If your browser is capable of 1.2 and your NetBotz appliance is running firmware 4.5.2 or higher, the connection should be made using TLS 1.2.
TLS auto-negotiates to the highest version
Product Line:
NetBotz
Environment:
Botsware version 4.5.2 to 4.7
Cause:
TLS versions 1.0, 1.1, and 1.2 are available on a number of versions of NetBotz firmware. Version TLS 1.2 was added in version 4.5.2 and TLS 1.0 was removed in version 4.6.4
Resolution:
Although version 1.1 is still available, whatever system connects to the NetBotz appliance should auto-negotiate to the highest version of TLS available on both systems. If your browser is capable of 1.2 and your NetBotz appliance is running firmware 4.5.2 or higher, the connection should be made using TLS 1.2.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.