Why am I being asked for a Password when connecting SoMove to an ATV320 drive using Ethernet or Profinet option cards?

Issue:
SoMove is requesting a password for an ATV320 drive before allowing a connection over Ethernet IP, ModBus TCP, or Profinet networks.

Resolution:
The password is not required when connecting SoMove via the ModBus port and also does not impact changes made through the keypad/display.

The default password should be visible on a label on the option card:

option card image

The default password can also be viewed (and the password can be reset back to default) through SoMove (via the ModBus port) or using one of the graphic display terminals (VW3A1101, VW3A1111 or VW3A1113).
Using the keypad: go to the Communication card settings and find parameter SEC.


d
To activate the security SPOL should be set to YES (default setting).
To reset the password back to default, change POWD to YES.
To display the default password look at DPW

During the first connection to the drive using the option card you will be prompted to change the password from default.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings