Is it possible to monitor the Ethernet Port Status of an HMIST6 in EcoStruxure Operator Terminal Expert

Issue:
Looking for an internal system variable that will reveal the status of the Ethernet port of an HMIST6

Product Line:
Harmony HMI, HMIST6, HMISTM6, EcoStruxure Operator Terminal Expert

Resolution:
Currently in EcoStruxure Operator Terminal Expert V3.2 SP1, there is no way to determine the status of the Ethernet port by the means of a built-in  Internal System Variable.

As a workaround, we could monitor the Quality property of an External Variable. Here are the different states that the Quality property could be in:

ValueDescription
0, 4

Access to device address and device address value is normal.

1, 3, 5, 7

Cannot access the device address.

8, 12

Device address value is invalid.

9, 13, 15

You cannot access the device address. Also, the device address value can be invalid.

2, 6, 10, 11, 14

Not in use



Here is an example script that will write the Quality property to a variable named "StatusVar". Note Var1 is our external variable.

blockly

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.