How can we help you today?

How do you assign the Output Contactor Command to the R2 relay on an ATV630 drive?

Resolution:

To assign the Output Contactor Command to relay R2, follow these steps:

  1. Verify that R2 Assignment is set to Not Assigned.

  2. Navigate to:
    Complete Settings > Generic Functions > Output Contactor CMD

  3. Set Output Contactor Assign to R2.

  4. Navigate to:
    Complete Settings > Error/Warning Handling > Output Phase Loss

  5. Set Output Phase Loss Assign to No Error Triggered.

The R2 relay is now assigned to the Output Contactor Command function.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings