How do you assign the Output Contactor Command to the R2 relay on an ATV630 drive?
Resolution:
To assign the Output Contactor Command to relay R2, follow these steps:
-
Verify that R2 Assignment is set to Not Assigned.
-
Navigate to:
Complete Settings > Generic Functions > Output Contactor CMD -
Set Output Contactor Assign to R2.
-
Navigate to:
Complete Settings > Error/Warning Handling > Output Phase Loss -
Set Output Phase Loss Assign to No Error Triggered.
The R2 relay is now assigned to the Output Contactor Command function.