Control Expert 15 returns error 'mfc140u.dll is missing' when starting
Control Expert returns the error 'system error: mfc140u.dll is missing' when trying to start.
This error will occur if the mfc140u.dll file already exists on the PC and it is of a newer version when Control Expert is installed. The 'mfc140u.dll' file is part of the 'Microsoft Visual C++ 20xx Redistributable ' libraries that gets installed during the Control Expert installation process. Per Microsoft rules, a software installation is not allowed to overwrite an existing version of a Microsoft '.dll' with an older version. This rule prevented the
proper installation of the required 'Microsoft Visual C++ 20xx Redistributable ' libraries.

The specific version 'mfc140u.dll' file is essential for the registration of other '.dll's that are included with Control Expert. As a result of this, the error could also be accompanied with the following error:

To resolve the issue,
This error will occur if the mfc140u.dll file already exists on the PC and it is of a newer version when Control Expert is installed. The 'mfc140u.dll' file is part of the 'Microsoft Visual C++ 20xx Redistributable ' libraries that gets installed during the Control Expert installation process. Per Microsoft rules, a software installation is not allowed to overwrite an existing version of a Microsoft '.dll' with an older version. This rule prevented the
proper installation of the required 'Microsoft Visual C++ 20xx Redistributable ' libraries.
The specific version 'mfc140u.dll' file is essential for the registration of other '.dll's that are included with Control Expert. As a result of this, the error could also be accompanied with the following error:
To resolve the issue,
- Rename the existing .'mfc140u.dll' file.
- Uninstall Control Expert.
- Reboot the PC.
- Reinstall Control Expert.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.