How can we help you today?

Why, after an application full download, some Modbus I/O scanning variables written to devices and driven by a BMENOC03x1 are not correct (bytes swapped) ?

This problem is a known issue and fixed in firmware revisions :
- SV1.05 for BMENOC0321
- SV2.16 for BMENOC0301 and BMENOC0311

The issue occurs when all conditions below are met :
- when using firmware revisions lower than the ones described above
- when re-configuring and re-downloading application with a Modbus IO Scanner configuration into a BMENOC3xx (without doing a power cycle after the download)
- IO Scanner configuration contained a mix of "Read ONLY", "Write ONLY" and "Read/Write" modbus request
- some IO Scanner lines have been deleted and/or added

=> These four conditions may cause byte swapped data (for little endian conversion) on some modbus commands on the I/O scanning devices.

A global power cycle on the rack or hot swap of BMENOC03x1 makes the issue disappear.

We recommend to upgrade the BMENOC03x1 firmware to the latest available version.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.