How can you read outlet pressure high alarm on the ATV630 drives over serial communications?
Resolution:
ST08 address is 16108 and bit 5 will give you high alarm status.
Bit 0: (DRYA) : Dry Running Alarm
Bit 1: (PLFA) : Pump Low Flow Alarm
Bit 2: (HFPA) : High Flow Alarm
Bit 3: (IPPA) : Inlet Pressure Protection Alarm
Bit 4: (OPLA) : Outlet Pressure Low Alarm
*Bit 5: (OPHA) : Outlet Pressure High Alarm
Bit 6: (PCPA) : Cyclic Start Protection Alarm
Bit 7: (JAMA) : Antijam alarm is raised
Bit 8: (LFA) : Low Flow Alarm
Bit 9: (LPA) : Low pressure alarm is raised
Bit 10: (FSA) : Flow limit function activated (FL_Mode_On)
Bit 11: (OPSA) : Outlet Pressure High Switch Alarm
Bit 12: (MPCA) : Multi-pumps Capacity Alarm
Bit 13: (MPLA) : Multi-pumps Lead Alarm
Bit 14: (LCHA) : Level Control High Level Alarm
Bit 15: (LCLA) : Level Control Low Level Alarm
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.