What is an INFL error on the ATV340 drive?

Possibly an internal time clock error. Communication error between keypad and drive or a clock oscillator start failure.

Reinitialize the communication by following steps.

  1. Power off the drive and wait until display is blank and repower on to confirm issue.
  2. Disconnect keypad from the drive and remove batter if applicable.
  3. If problem persists, try a different keypad if possible.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.