How can we help you today?

How can you program a Jog function, in a ATV212 drive?

Issue:

Programming a Jog function, in a ATV212 drive.

Product Line:

ATV212

Environment:

Jog

Cause:

n/a

Resolution:

This drive does not have a jog function, in the menus. You would need to program a Preset Speed. Go to F113 (RES) and set to 6 and set SR1 to 10 ( or whatever jog speed you need?). When F and RES goes high, should run at the jog speed.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings