How can we help you today?
Is it possible replace a PRM without Control Expert?
Yes, it is possible.
In theControl Expert application, under PRM general settings, ensure the following options are checked and properly configured:
- Create an entry for this device name in the DHCP server
- Backup the PRM configuration in the FDR server on download
Once these settings are confirmed, follow these steps to correctly replace the PRM:
- Remove the PRM module to be replaced.
- Prepare the new PRM module:
- Set its lower rotary switch to ‘E’ (Configuration file deletion) to clear any existing configuration.
- Power up the new PRM and wait for the boot process to complete, then power it off.
- Match the rotary switch positions:
- Check the rotary switch positions on the old PRM and set the new PRM identically.
- Install the new PRM:
- Power up the new PRM in the same location as the old one.
The new PRM will boot and automatically retrieve its configuration file from the FDR server.
Released for: Schneider Electric USA
Explore more
Product:
Explore more
Product:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.