Why is the "œ" character not displayed correctly during EcoStruxure Operator Terminal Expert runtime?

Issue:
Character "œ" appears incorrectly during Runtime

Product Line:
EcoStruxure Operator Terminal Expert, Harmony HMI,

Resolution:
The language fonts on EcoStruxure Operator Terminal Expert are regulated by ISO standards.

The French_Gothic font set uses the character code [ISO IEC8859-1]. The "œ" character can not be displayed because it is a character that does not exist in the [ISO IEC 8859-1] character code.

Instead, use the Romanian_Gothic font set. This uses the character code [ISO IEC8859-16] which includes the "œ" character.

Schneider Electric USA