PowerChute Network Shutdown Appliance: Events logged for host shutdown and maintenance mode are disappearing after PCNS restart

Issue:
Events logged for host shutdown and maintenance mode are disappearing after a PowerChute restart.

Products:
PowerChute Network Shutdown v4.3 and 4.4.2

Note: We recommend installing PowerChute version 4.4.3, configuring it, and then discontinuing the use of the older version. PowerShell and the PowerCLI have been preinstalled on PowerChute version 4.4.3, so when reviewing the script instruction, you can skip to the section to download settings.txt, disable_HA.ps1, and enable_HA.ps1 files.

Environment:
VMware vSphere 7U1 and above with vCenter Server 7U1 and above.

Cause:
Hard shutdown of PowerChute Network Shutdown Appliance when the host goes down.

Solution:
When the PowerChute Network Shutdown appliance is on the local datastore.


Enable automatic startup and shutdown for the PowerChute Network Shutdown appliance and set shutdown behavior to Guest Shutdown with a 120-second delay.

VM Startup Shutdown Image

When the PowerChute Network Shutdown appliance is on a shared datastore.

Configure PowerChute Network Shutdown with the attached scripts (enable_HA and disable_HA).  Please follow the instructions in the attached PDF (HA_ScriptInstructions).

NOTE: If vSphere Cluster Services (vCLS) is enabled on the cluster, the attached script will handle vCLS VMs as well.  For more information on using the script for vCLS, refer to KBase article FA416409.

Schneider Electric USA

Attachment(s)
settings.txt [229 Bytes]
HA Scripts.zip [1.96 KB]
HA_ScriptInstructions.pdf [247.28 KB]
HA Scripts.zip [2.19 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings