What does NLP mean on an ATV340 drive, and how do I fix it?

Issue:

On an ATV340 drive, NLP (No Line Power) indicates that the drive is detecting low or missing input voltage, resulting in insufficient DC bus voltage.

Why this happens:

  • The drive is not receiving proper voltage at its input terminals
  • The DC bus voltage is too low for normal operation

How to troubleshoot the NLP status:

1. Check input power supply

  • Measure voltage at terminals L1, L2, and L3
  • Confirm the supply voltage matches the drive rating and is stable

2. Verify voltage readings in the drive

  • Access the MON (Monitoring) menu
  • Check ULn (Mains Voltage) to see what the drive detects
  • Compare it with your actual measured voltage

3. Measure DC bus voltage

  • Check voltage across PA+ and PC- (if available)
  • Validate using this formula:
DC Bus Voltage ÷ 1.414 ≈ AC Mains Voltage

Example:

For a 230 V drive:
DC bus ≈ 324 VDC
324 ÷ 1.414 ≈ 230 V

If the issue persists:

  • Inspect wiring and connections for damage or looseness
  • Check for blown fuses or supply interruptions
  • Contact Schneider Electric support for further assistance

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.