How can we help you today?
Why do I have a "Communication Error" When Opening LOGINSERTER Node with PME Designer ?
Product Line
Power Monitoring Expert 2022
Power Monitoring Expert 2021
Power Monitoring Expert 2020
Power Monitoring Expert 9.0
_____________________________________________________________
Environment
Designer
Log Acquisition Module
_____________________________________________________________
Issue
When opening the LOGINSERTER Node with PME Designer a "Communication Error" message box is displayed.
In the system log you will see a CRITICAL error stating ‘Caught: ‘Parse Error Caught parse error 6 during PICType: write’ file C:\Dev\agent2\work\26\s\PEGASYS\src\pegasys\vip\kernel\server\progman.cpp line 160'
_____________________________________________________________
Root Cause
If you are using the Log Inserter in ‘Input Logs’ mode and linking device data recorders to a Log Acquisition module, it is possible to see this error if there are an extremely large number of inputs (possibly greater than 3000).
_____________________________________________________________
Proposed Solution
Create multiple Log Acquisition Modules.
Do not link more than 3000 Inputs on each Log Acquisition Modules.
Released for: Schneider Electric USA
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.