How can we help you today?
Why can't I open my .STU file but .STA works using CE V15.0 ?
Issue
When upgrading a Control Expert project created with a version earlier than V14.1 to Control Expert V15, an issue may occur if the project contains password-protected elements.
The issue may be related to one of the following configurations:
- Password protection is configured without a password.
- Password protection is configured with an empty password.
These configurations are no longer allowed in Control Expert V15 and later.
Product Line
EcoStruxure Control Expert
Environment
- Project originally created with a Control Expert version earlier than V14.1
- Project opened or upgraded with Control Expert V15
Resolution
Two possible resolutions are currently identified:
Option 1: Upgrade Control Expert
Upgrade to Control Expert V15.1, where this issue is reported as corrected.
Option 2: Remain on Control Expert V15
If Control Expert V15 must be retained:
- Export the affected DFBs.
- Reimport the DFBs into the project.
- Verify that the project can then be processed without the password-related issue.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.