My HMIST6 is not booting, is there a way to recover it?
Issue
The HMIST6 does not boot, it stays on a loading screen with a blue circle.
Product Line
HMIST6 series, HMISTM6 series and HMISTO series.
Environment
HMI programmed with EcoStruxure Operator Terminal Expert 3.2 SP2 and newer.
Cause
In some cases, when a display unit failed to accept the project in a transfer operation, the HMI cannot boot and Recovery Mode must be opened.
Resolution
Here are the steps to access Recovery Mode:
1. Power off the HMI.
2. Power on the HMI.
3. While it is booting and the screen shows the green loading bar, touch and hold the bottom-left corner or bottom-right corner of the display until a dialog box asking "Do you want to enter recovery mode?" appears. It takes about 10 seconds for the dialog box to show up.
3. Click [Yes] to enter recovery mode.
4. Transfer the project, depending on your transfer method.
This recovery process was introduced on EOTE v3.2 SP2. It will not work with HMIs programmed with older versions of EcoStruxure Operator Terminal Expert.
Please contact technical support if further assistance is needed after trying this procedure.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric USA
Explore more
Product:
Explore more
Product:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.