How is the undervoltage (underload) level configured on an ATV212 drive—in amps or percentage?

Resolution:

The undervoltage (underload) detection level on the ATV212 drive depends on the configuration of parameters:

  • F610: Enables underload detection.
  • F611: Sets the underload level.
  • F701: Determines the unit used for F611.

By default, F611 is set in amperes (A).


If you change F701 to 0, the underload level in F611 will instead be set as a percentage (%) of the drive’s rated current (In).