How can we help you today?

What class of fuse do ALL the 60 A, 240 Vac max, heavy duty safety switches accept?

Product Line:
Heavy Duty Safety Switches

Resolution:
HDSS = heavy duty safety switches
SCCR = short circuit current rating

ALL the 60 A, 240 Vac max, HDSS accept Class H or K fuses as standard. Options include Class R fuses (field install Class R Fuse Kit).  With Class H or K fuses installed, the switches are UL/CSA listed for use on systems with up to 10,000 RMS Symmetrical Amperes available fault current. With Class R fuses (and Class R Fuse Kit installed), the switches are UL/CSA listed for use on systems with up to 200,000 RMS Symmetrical Amperes available fault current.

NOTES:
1) DO NOT USE RENEWABLE LINK FUSES IN SQUARE D SAFETY SWITCHES. The use of renewable link fuses may adversely affect user safety, impair reliability, and will void the warranty.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings