How can we help you today?

What is accessory 31BG?

Accessory 31BG is a Status Relay Bundle that provides a relay (3 total) for each of the following statuses:
  • Normal Source Acceptability
  • Emergency Source Acceptability
  • Pre & Post Transfer Signal
Each relay has 2 NO/NC (Form C) sets of contacts rated for 6A at 120Vac, 250Vac Max.

Please see below for a more detailed accessory description and screen short from a sample wiring diagram.
31BG accessory description

31BG wiring diagram
Please click here for the Group 5 Control Panel User's Guide

For further information you contact Technical Support at 1-800-800-2726 then dial 3 or send an email to technicalsupport@ascopower.com.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings