What is the Branch Circuit Power Meter with Ethernet communications module integrated (BCPME) Graphic User Interface (GUI) login credential?
Issue
A user cannot access the PowerLogic BCPME embedded web interface during initial device configuration.
Product Line
PowerLogic BCPME
Environment
BCPME embedded web interface
Initial installation and configuration
Ethernet communications
Cause
The username or device-specific password required for initial access is unknown.
Resolution
The BCPME is configured with the following default network settings:
IP address: 192.168.1.24
Subnet mask: 255.255.255.0
Configure the computer with a compatible static IP address and subnet mask, then connect to the BCPME embedded web interface.
Use the following username:
Username: admin
The initial password is a unique alphanumeric password assigned to each device. The password is printed on the barcode label attached to the product enclosure.
After the initial login, change the password according to the site cybersecurity requirements.
Refer to the attached BCPME User Guide for network setup, initial access, and web-interface configuration details.