ATV320: Configuring a Custom Parameter for Display on the Graphic Display Terminal Using SoMove
Resolution:
In SoMove, click on the Device menu and select ATV320 HMI Personalization.
- To make navigation easier, collapse menus by clicking the – sign and expand them by clicking the + sign.
Configure the Scaling Factor
Determine the appropriate scaling factor based on the application.
For example, if the conveyor belt operates at 26.46 meters/minute at 60 Hz, the scaling factor is:
60.0 Hz × 0.441 meters/minute per Hz = 26.46 meters/minute
Configure the parameter as follows:
- Short Label: Conveyor Speed
- Units: m/M (3 characters maximum)
- Scaling Factor: 0.441
Click Validate to apply the customization.
Once complete, click OK at the bottom of the Personalization window to save the settings, and save a copy of the SoMove project file.
If these changes are made while connected to the drive, make sure SoMove is synchronized with the drive. After updating the settings, either cycle power to the drive or disconnect and reconnect the Graphic Display Terminal.
-
Configure the Graphic Display Terminal
To display the customized parameter on the Graphic Display Terminal:
- Press ESC until the Main Menu is displayed.
- Select Menu 3: Interface and press OK.
- Select Menu 3.3: Display Configuration and press OK.
- Select Display Screen Type.
- Choose the desired display format:
- Digital: Up to 2 parameters
- Bar Graph: Up to 2 parameters
- List: Up to 5 parameters
- Press ESC once, then select Parameter Selection and press OK.
- Scroll through the available parameters and select the parameters to be displayed.
- After power is applied, the drive will briefly display the standard drive menus and then automatically switch to the selected parameter display.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)