How can we help you today?

Why are the OPC UA client values not updating when using the UA_ReadList function block?

Changing the value type of the OPC UA client may prevent the client values from updating.

Performing the following steps may resolve the issue:
  1. Export the project as a .ZEF file
  2. Import the .ZEF file
  3. Run a Rebuild All project
  4. Download Project to controller

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings