How to Use the Small Motor Test [SST] Function on an ATS480 Soft Starter
Resolution:
The Small Motor Test [SST] parameter is located under Menu 3 [Complete Settings] > 3.3 [Motor Wiring].
This parameter allows the ATS480 to be tested using a small motor. When [SST] is set to YES, phase loss monitoring [PHP] is disabled and Control Mode [CLP] is automatically forced to Voltage Control. This allows the soft starter to start normally when a run command is applied. During the test, the display terminal will indicate [Small Motor Test] SST.
The [SST] parameter automatically resets to NO after a power cycle.
In SoMove ATS480 DTM version 1.1.10.0, the [SST] Small Motor Test parameter is not currently visible. Therefore, this parameter must be changed directly from the ATS480 keypad. At this time, it is unknown whether [SST] will be made available through SoMove in a future DTM version.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance: