How to Use the Small Motor Test [SST] Function on an ATS480 Soft Starter

Resolution:

The Small Motor Test [SST] parameter is located under Menu 3 [Complete Settings] > 3.3 [Motor Wiring].

This parameter allows the ATS480 to be tested using a small motor. When [SST] is set to YES, phase loss monitoring [PHP] is disabled and Control Mode [CLP] is automatically forced to Voltage Control. This allows the soft starter to start normally when a run command is applied. During the test, the display terminal will indicate [Small Motor Test] SST.

The [SST] parameter automatically resets to NO after a power cycle.

In SoMove ATS480 DTM version 1.1.10.0, the [SST] Small Motor Test parameter is not currently visible. Therefore, this parameter must be changed directly from the ATS480 keypad. At this time, it is unknown whether [SST] will be made available through SoMove in a future DTM version.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings