How can we help you today?

Machine Expert, need information about User Data Type limitations. Arrays and structures complexity and size.

Issue:

Need to know the limitations for Arrays and Structures complexity and size in EcoStruxure Machine Expert.

Product:

EcoStruxure Machine Expert software (all versions).

Answer:

EcoStruxure Machine Expert/Codesys does not limit the max array size or structure complexity.

The only limitation is the memory size of the controller.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings