How can we help you today?

Why does Machine Expert Simulation ask for login user and password ?

If Simulation on Machine Expert asks for the user to log in and enter the password it is caused by the user accidentally creating a username and password while using simulation mode.

To remove the username and password follow the steps below.

  1. Save the project you are working on in Machine Expert.
  2. Close Machine Expert
  3. Open the Windows file browser and navigate to the folder C:\ProgramData\CODESYS ( ProgramData folder may be hidden. If hidden then in the Windows file browser windows click on the "View" tab, in the view options find the radio button for "Hidden items" and put a check mark in this option the show hidden items )When the   ProgramData folder is visible open the folder and find the CODESYS folder and open this folder.
  4. Delete the folder "Simulation" from the CODESYS folder
  5. Close the file browser window.
  6. Launch Machine Expert. open your project and test Simulation Mode again. You will not be required to enter a username and password.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings