What is the minimum front clearance required for Size 6 ATV630 and ATV930 drives?

Resolution:

A minimum clearance of 100 mm or more is required in front of Size 6 ATV630 and ATV930 drives.

This space is necessary because these drives have front ventilation openings that rely on natural air convection to maintain proper cooling within the electrical enclosure.

The 100 mm requirement is based on thermal validation testing conducted during the product development phase to ensure safe and efficient operation.

Size 6 frame size