How can we help you today?

How to get control wire tapped lugs for the Powerpact M, P, or R frame breakers?

Product Line:

Powerpact Circuit Breakers

Answer:

For control wire tapped lugs, add suffix T before the K on the part number of the lugs (e.g. AL800P7TK for the control wire tapped version of AL800P7K).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings