For Tesys Island, what is the accuracy of Current Measurement?

Issue:
Unable to find current accuracy for Tesys Island systems

Product Line:
Motor Management system Tesys Island

Environment:
IEC Contactors and Starters

Resolution:
Per our technical literature and marketing specs, all we publish is an energy monitoring accuracy which is 10% for loads running under nominal conditions(50–125%FLA, power factor 0.7, 47–63Hz).

The current measurement is accurate enough to satisfy all protection functions per UL/IEC 60947-4-1 and to satisfy this 10% energy monitoring requirement. This represents various accuracies at various levels of current relative to FLA. Not published: Under nominal environmental conditions, at 50 or 60hz, and running near FLA, the current measurement is 2% accurate.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings