How can we help you today?

Why does the HDPM6000 have duplicate Modbus registers listed

Issue:

Why does the HDPM6000 have duplicate Modbus registers listed?

Product Line:

HDPM6000

Environment:

HDPM6000 Modbus Register Map

Cause:

The Modbus Register list provides two Modbus registers with the same alarm register with two different Modbus register addresses.

For example: 10220-10227 - Warning and 10820-10831 - Warning.

What is the difference for these two sets of alarm registers?

Resolution

Some registers are legacy and only support up to 120 circuits.  (i.e. 10220-10227)

The new registers now support the new features of the HDPM6000 and a total of 192 Circuits. (i.e. 10820-10831)

HDPM6000 Protocol and Modbus Guide: PowerLogic™ HDPM6000 Protocol Guide | Schneider Electric

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings