What is the inrush for an EX150T3HCUNLP?

Issue:

Inrush for EX150T3HCUNLP

Product Line:

Low voltage Transformer

Environment:

Products sold in North America

Resolution:

The inrush of an EX150T3HCUNLP is 7.6 times the Full Load Amperage (FLA) of the Primary. The Primary FLA (at 480V) is 180A. 180A x 7.6 = an Inrush of 1,368A.