How can you read the serial number of ATV630 and ATV930 drives via Modbus or Ethernet?

Resolution:

You can retrieve the drive’s serial number through Modbus or Ethernet communication by reading specific parameters and converting their values.

Steps:

  1. Read parameters C1P1 to C1PA (logical addresses 3410 to 3419).
  2. Each parameter returns a HEX value (2 bytes per word).
  3. Convert each HEX value to ASCII.
  4. Combine the ASCII values in order to reconstruct the full serial number.

Example:


Serial number: 4002200HL444562001

C1P1 (3410) = 0x3430 → 40
C1P2 (3411) = 0x3032 → 02
C1P3 (3412) = 0x3230 → 20
C1P4 (3413) = 0x3048 → 0H
C1P5 (3414) = 0x4C34 → L4
C1P6 (3415) = 0x3434 → 44
C1P7 (3416) = 0x3536 → 56
C1P8 (3417) = 0x3230 → 20
C1P9 (3418) = 0x3031 → 01
C1PA (3419) = 0x0000 → --

Result:


Combine all ASCII outputs to obtain the full serial number.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings